All of the R-407-series refrigerants are based on blends of the three HFC refrigerants R-32 (difluoromethane), R-125 (pentafluoroethane) and R-134a described above. R-407C has been formulated as a good match to the existing HCFC refrigerant R-22 for use in air conditioning, chilling and refrigeration applications and is the first of the R-22 alternatives to be used on a commercial scale. Suitable for retrofit and original equipment usage.
Composition (wt%) R-32/R-125/R-134a = 23/25/52
Please note that not all products are available in all markets.
R-407C Physical Properties
Property |
S.I. Units |
British Units |
Bubble Point |
-44.0 (°C @1 atm) |
-47.2 (°[email protected]) |
Dew Point |
-36.8 (°C @1 atm) |
-34.2 (°[email protected]) |
Evaporator Glide |
4.8 (°C @1 atm) |
8.6 (°[email protected]) |
Bubble Point Pressure |
11.9 (bara @ 25°C) |
172.6 (psia@70°F) |
Critical Temperature |
86.0 (°C) |
186.8 (°F) |
Latent Heat Vaporisation |
193.9 (kJ/kg @25°C) |
83.4 (Btu/lb @70°F) |
Coeff. Vol. Therm. Exp. |
0.0037 (K-1 0-20°C) |
0.0019 (°F-1 40-80°F) |
Saturated Vapour Density |
4.57 (kg/m³@nBpt) |
0.285 (lb/cuft @nBpt) |